Conversion kits LIDER, LIDER EVG
• Fluorescent lamp power range 6–80 W (depends on a model)
• Maximum charging time: 24 h
• Emergency operation time: 1, 3 h
• The built-in automatic switching system enables continuous operation of the fluorescent lamps with regular power supply as well as in the emergency mode
• The process of charging and proper battery connection is signalled by a LED while supplying the system with main voltage
• The simplest and the cheapest way for emergency lighting
Conversion kits LIDER autotest
Test types:
• Test A is run automatically every 30 days.
• Test A checks the following parameters:
• Enforcing emergency operation of the frame for 5 minutes
• Control of battery power discharge
• Control of minimum voltage of battery
• Test B is run automatically every 360 days
• Test B checks the following parameters:
• Enforcing emergency operation of the frame for all duration time (1, 3 h)
• Control of battery power discharge
• Control of minimum voltage of battery
In case of power cut during TEST A or B the unit operates under emergency lighting power. Test signalling continues. After the 230V AC power is on again the unit remains in emergency lighting mode until a full cycle of TEST A or B is completed.