Monitoring system RUBIC

In buildings where there is a need for installing a large number of independent emergency lighting fittings, there is always a problem connected to the process of controlling the condition of the fittings. Manual controlling of the condition of the fittings requires a lot of time and may sometimes disturb the regular use of the premises. RUBIC system, designed to monitor the operation of emergency fittings with independent power sources, was created to solve this problem. Modern solutions of the Rubic system allow for the configuration and control of the condition of the fittings from one place.

C-RUBIC control unit:
  • Standard monitoring of 250 fittings, expansion within the standard unit up to 1000 fittings
  • Centronix printer connector, LCD monitor
  • 230V 50Hz power supply, charge time - 24h
  • Communication through a screened cable 2x0,5 mm2
  • Distance between the control unit and the furthest fitting - 1200 m2 (or applying RPT)

  • Lighting fittings working under the RUBIC system have unique addresses and are connected to C-Rubic control unit with a communication cable. The fittings communicate with the central unit reporting any abnormalities which are signalled on the central unit display with LED diodes placed on the central unit panel.

Test types: the same as LIDER autotest

The frequency of running tests A and B may be programmed according to the needs of the user. There is a possibility of programming the tests with exact dates of when they should be carried out. Long tests B should be run when the premises are not to be used within 24 hours after finishing the test. This time is needed for the recharging of the batteries discharged during the long test.

Test results are stored in the memory of the central unit and may be viewed on the central unit's display. Test reports may be printed with the PR-RUBIC printer or any printer using LPT connector (Centronix)